Data sheet, Tg01 – Procom TG01 User Manual
Page 3
![background image](/manuals/290602/3/background.png)
Data Sheet
TG01
Signal Generator
A 125 Hz sine signal is generated on the TG01 module. This signal is isolated gal-
-
to the loudspeaker circuit to be
mpedance measuring is described in the 4LSL data sheet.
ystem.
he earth leakage recognition on the TG01 is only active during an impedance
with the TG01 is an earthed
vanically from the control block, amplified by a transformer, and passed over the out
put transformer to the measuring module 4LSL.
The 4LSL passes the reference signal over relays
measured.
More about i
The reference signal can be used by multiple 4LSL modules in the s
T
measuring cycle. An earth leakage can be localized since impedance measuring is
always done in respect to the loudspeaker circuit. When earth leakage is occurring in
the loudspeaker circuit being tested it is detected over the opto-coupler input of the
TG01. Earth leakage is signalled by a red LED on the front plate of the module and
passed to the 4LSL. When impedance measuring by the 4LSL is finished then the
earth leakage LED on the TG01 switches off.
A requirement for monitoring earth leakage
+potential.
The Symbols on the Front Plate and their Meaning:
The System Blinker
ssor taking place
Addressing from proce
I/O Input/Output
s push-push operation with the system
ut works as push-pull operation with the system blinker
BUS output works a
blinker
BUS inp
Test1 Test Signal
being sent
Test signal is
Test2 Operating Voltage
Has operating voltage
Al1
Not in Use
Al2
Earth
Leakage
e tested loudspeaker circuit
Earth leakage on th
Date
27.03.2009 Page:
3/4 Author:
HS
Document-No.:
DB_TG01_2831_02
© 2008 ProCom, All rights and technical changes reserved