7. Trouble Shooting

If the UPS system does not operate correctly, first check the operating
information on the LCD display.

Please attempt to solve the problem using the table below. If the problem
still persists, consult your dealer.

7.1 Trouble Shooting According To Warning Indication

Problem Displayed

Possible cause

Remedy

Epo Active

Alarm code:71

EPO connector is closed Check the EPO connector status

On Maintain Bypass

Alarm code:72

Maintain bypass switch
is open

Check the maintain bypass switch
status

Battery Disconnect

Alarm code:11

Battery pack is not
connected correctly

Do the battery test to confirm.
Check the battery bank is
connected to the UPS.
Check the battery breaker is turn
on.

Battery low

Alarm code:12

Battery voltage is low

When audible alarm sounding
every second, battery is almost
empty.

Output Overload

Alarm code:41

Overload

Check the loads and remove some
non-critical loads.
Check if some loads are failed.

Fan Failure

Alarm code:84

Fan abnormal

Check if the fan is running
normally.

Charger Fail

Alarm code:15

The charge fails

Consult dealer.

Over Charge

Alarm code:14

Battery is over charged

The UPS will turn off the charger
until the battery voltage is normal

Model Pin Error

Alarm code:92

UPS internal fault

Consult dealer.