2 single chamber housing, 3 connection example – VEGA VEGABAR 87 Save sensor - Quick setup guide User Manual

Page 9

background image

9

4 Connecting to power supply

VEGABAR 87 • Slave sensor for electronic differential pressure

46335-EN-131125

7. Check the hold of the wires in the terminals by lightly pulling on

them

8. Connect the screen to the internal ground terminal, connect the

outer ground terminal to potential equalisation

9. Tighten the compression nut of the cable entry gland. The seal

ring must completely encircle the cable

10. Reinsert the display and adjustment module, if one was installed
11. Screw the housing cover back on
The electrical connection is finished.

4.2 Single chamber housing

The following illustration applies to the non-Ex, Ex-ia and Ex-d ver-

sion.

5 6 7 8

4

2

1

Master

Fig. 4: Wiring plan VEGABAR 87 Slave sensor
1 To the sensor

2 Ground terminal for connection of the cable screen

1)

4.3 Connection example

5 6 7 8

4

2

3

1

4

5

1

2

+

( )

(-)

6 7 8

4...20mA

Fig. 5: Connection example VEGABAR 87 slave sensor
1 VEGABAR 87

2 VEGABAR 87 slave sensor

3 Connection cable

4 Supply and signal circuit VEGABAR 87

Electronics and terminal

compartment

Connection example,

slave sensor

1)

Connect screen here. Connect ground terminal on the outside of the housing

to ground as prescribed. The two terminals are galvanically connected.