5 Set up with the display and adjustment module
VEGABAR 87 • Slave sensor for electronic differential pressure
46335-EN-131125
The quick setup for differential pressure measurement is finished.
4. Unit, static pressure
In this menu item, you determine the unit of the static, i.e. superim-
posed pressure.
5. Position correction
In this menu item you compensate the influence of the installation
position of the instrument (offset) on the measured value.
6. Distance
In this menu item, you enter the installation distance between master
and slave sensor.
7. Min. adjustment
In this menu item you carry out the min. adjustment for density.
Enter the percentage value and the corresponding density value for
the min. density.
8. Max. adjustment
In this menu item you carry out the max. adjustment for density.
Enter the percentage value and the corresponding density value for
the max. density.
The quick setup for density measurement is finished.
4. Unit, static pressure
In this menu item, you determine the unit of the static, i.e. superim-
posed pressure.
5. Position correction
In this menu item you compensate the influence of the installation
position of the instrument (offset) on the measured value.
6. Distance
In this menu item, you enter the installation distance between master
and slave sensor.
7. Min. adjustment
In this menu item, you carry out the adjustment for the min. height of
the interface.
Enter the percentage value and the corresponding height of the
interface.
8. Max. adjustment
In this menu item, you carry out the adjustment for the max. height of
the interface.
Enter the percentage value and the corresponding height of the
interface.
Quick setup - Density
measurement
Quick setup - Interface