SAFETY
Location of module
Safe area, Zone 2, IIC T4 hazardous area or Class 1, Div 2,
Groups A, B, C, D T4 hazardous location.
Location of field wiring
Zone 1, IIB T4 hazardous area or Class 1, Div 1, Groups C, D
T4 hazardous location.
Field wiring protection
Intrinsically safe
Certification Code
II(2) GD [EEx ib] IIB, II 3 GD EEx nA IIB T4.
Safety description
14.8V, 359mA, 5.31W, 0.50
µF*, 550µH*
FM entity parameters
14.8V, 359mA, 5.31W, 0.50
µF*, 550µH*
ATEX certificate numbers
MTL02ATEX9122
BAS02ATEX7277
FM certificate number
J.I.3012571
Certification is compatible with
Fieldbus FOUNDATION FF816-FISCO.
IEC/TS 60079-27 FISCO Technical Specification.
MECHANICAL
Mounting
DIN rail/surface mounting
Module width
42mm
Weight
360g
LED INDICATORS
OFF
ON
Power (green)
Power fail
Power OK
Fault (red)
Normal
Fault
Host Comm (yellow)
Comms failure
Comms OK
IS Comm (yellow)
Comms failure
Comms OK
9122-IS FISCO POWER
SUPPLY - IIB
◆
◆ Typically more than 12 IS fieldbus
devices per power supply
◆
◆ Fieldbus repeater
◆
◆ Multidrop isolators on single fieldbus link
◆
◆ Power, fault and repeater LEDs
◆
◆ 250V ac input/output/power supply
isolation
◆
◆ Switch selectable terminator on host side
◆
◆ Fixed terminator on IS side
◆
◆ Switch selectable power for host side
◆
◆ Mountable in Zone/Division 2
MODULE SPECIFICATION
See also System Specification
OUTPUT
Number of channels
One
Voltage
12.8V (min.) at 0°C (see note)
Design Current
0 to 265mA
Output ripple
Complies with clause 22.6.2 of the fieldbus standard†
Minimum load
No load
Maximum cable length
Determined by IS load, see Application Note AN9026 for details
Isolation
Input to output:
250V ac rms
Input and output to power supply:
250V ac rms
U
m
= 250V rms
INPUT
Input voltage
19.2 - 30V dc
Current consumption
380mA (typical) 495mA (max.) at 20V
315mA (typical) 410mA (max.) at 24V
255mA (typical) 330mA (max.) at 30V
Power dissipation with 250mA load
4.1W (typical) 6W (max.)
Input protection
Fuse + supply reversal diode
*
When used in accordance with IEC 60079-27, there is no need to take into
consideration Co and Lo.
Note: Temperature coefficient 12mV/°C. If operated below 0°C, the reduced resistance of
the fieldbus cable more that compensates for the reduction in voltage available.
Fieldbus Foundation™ and FOUNDATION™ are trademarks of Fieldbus Foundation, Austin, Texas, USA.
†
The applicable fieldbus specifications and standards are:
— FOUNDATION™ Fieldbus 31.25 kb/s Physical Layer Profile
Specification, document FF-816.
—
IEC 61158-2: 2000.
—
ISA-S50.02-1992 for 31.25 kb/s fieldbus systems.