beautypg.com

9122-is fisco power supply - iib – VEGA 912X-IS FISCO POWER SUPPLIES User Manual

Page 3

background image

EUROPE (EMEA)

Tel: +44 (0)1582 723633

Fax: +44 (0)1582 422283

AMERICAS

Tel: +1 603 926 0090

Fax: +1 603 926 1899

ASIA PACIFIC

Tel: +65 487 7887

Fax: +65 487 7997

E-mail: [email protected] Web site: www.mtl-inst.com

May 2003

SAFETY

Location of module

Safe area, Zone 2, IIC T4 hazardous area or Class 1, Div 2,
Groups A, B, C, D T4 hazardous location.

Location of field wiring

Zone 1, IIB T4 hazardous area or Class 1, Div 1, Groups C, D
T4 hazardous location.

Field wiring protection

Intrinsically safe

Certification Code

II(2) GD [EEx ib] IIB, II 3 GD EEx nA IIB T4.

Safety description

14.8V, 359mA, 5.31W, 0.50

µF*, 550µH*

FM entity parameters

14.8V, 359mA, 5.31W, 0.50

µF*, 550µH*

ATEX certificate numbers

MTL02ATEX9122
BAS02ATEX7277

FM certificate number

J.I.3012571

Certification is compatible with

Fieldbus FOUNDATION FF816-FISCO.
IEC/TS 60079-27 FISCO Technical Specification.

MECHANICAL

Mounting

DIN rail/surface mounting

Module width

42mm

Weight

360g

LED INDICATORS

OFF

ON

Power (green)

Power fail

Power OK

Fault (red)

Normal

Fault

Host Comm (yellow)

Comms failure

Comms OK

IS Comm (yellow)

Comms failure

Comms OK

9122-IS FISCO POWER
SUPPLY - IIB

Typically more than 12 IS fieldbus

devices per power supply

Fieldbus repeater

Multidrop isolators on single fieldbus link

Power, fault and repeater LEDs

250V ac input/output/power supply

isolation

Switch selectable terminator on host side

Fixed terminator on IS side

Switch selectable power for host side

Mountable in Zone/Division 2

MODULE SPECIFICATION

See also System Specification

OUTPUT
Number of channels

One

Voltage

12.8V (min.) at 0°C (see note)

Design Current

0 to 265mA

Output ripple

Complies with clause 22.6.2 of the fieldbus standard†

Minimum load

No load

Maximum cable length

Determined by IS load, see Application Note AN9026 for details

Isolation

Input to output:

250V ac rms

Input and output to power supply:

250V ac rms

U

m

= 250V rms

INPUT

Input voltage

19.2 - 30V dc

Current consumption

380mA (typical) 495mA (max.) at 20V
315mA (typical) 410mA (max.) at 24V
255mA (typical) 330mA (max.) at 30V

Power dissipation with 250mA load

4.1W (typical) 6W (max.)

Input protection

Fuse + supply reversal diode

*

When used in accordance with IEC 60079-27, there is no need to take into
consideration Co and Lo.

Note: Temperature coefficient 12mV/°C. If operated below 0°C, the reduced resistance of
the fieldbus cable more that compensates for the reduction in voltage available.

Fieldbus Foundation™ and FOUNDATION™ are trademarks of Fieldbus Foundation, Austin, Texas, USA.

The applicable fieldbus specifications and standards are:
— FOUNDATION™ Fieldbus 31.25 kb/s Physical Layer Profile

Specification, document FF-816.

IEC 61158-2: 2000.

ISA-S50.02-1992 for 31.25 kb/s fieldbus systems.