6 Set up with the display and adjustment module

VEGAFLEX 81 • Profibus PA

44214-EN-130910

Additional adjustments: Sensor address, PIN, date/time, reset,

copy sensor data
Info: Instrument name, hardware and software version, date of manu-

facture, instrument features
Note:

For optimum adjustment of the measurement, the individual submenu

items in the main menu item "Setup" should be selected one after

the other and provided with the correct parameters. If possible, go

through the items in the given sequence.
The procedure is described below.
The following submenu points are available:

The submenu points described below.

An address must be assigned to each Profibus PA instrument. Each

address may only be assigned once in the Profibus PA network. The

sensor is only recognized by the control system if the address is set

correctly.
When the instrument is shipped, address 126 is adjusted. This ad-

dress can be used for function test of the instrument and for con-

nection to a Profibus PA network. Then address must be changed to

integrate additional instruments.
The address setting is carried out either via:

The address selection switch in the electronics compartment of

the instrument (address setting via hardware)

The display and adjustment module (address setting via software)

PACTware/DTM (address setting via software)

The hardware addressing is effective if an address <126 is set

with the address selection switches on the electronics module of

VEGAFLEX 81. Software addressing thus has no effect - only the set

hardware address applies.

The software addressing is only effective if address 126 or higher is

adjusted on the instrument with the address selection switches.

Here you can assign a suitable measurement loop name. Push the

"OK" key to start the processing. With the "+" key you change the sign

and with the "->" key you jump to the next position.
You can enter names with max. 19 characters. The character set

comprises:

Setup - Instrument ad-

dress

Hardware addressing

Software addressing

Setup - Measurement

loop name