beautypg.com

VEGA VEGAFLEX 81 Profibus PA Coax probe User Manual

Page 16

background image

16

4 Mounting

VEGAFLEX 81 • Profibus PA

44214-EN-130910

In vessels with conical bottom it can be advantageous to mount the

sensor in the center of the vessel, as measurement is then possible

nearly down to the lowest point of the bottom. Keep in mind that

measurement all the way down to the tip of the probe may not be pos-

sible. The exact value of the min. distance (lower dead band) is stated

in chapter "Technical data".

Fig. 6: Vessel with conical bottom

Before beginning the welding work, remove the electronics module

from the sensor. By doing this, you avoid damage to the electronics

through inductive coupling.

Do not mount the instruments in or above the filling stream. Make sure

that you detect the product surface, not the inflowing product.

Fig. 7: Mounting of the sensor with inflowing medium

The reference plane for the measuring range of the sensors is the

sealing surface of the thread or flange.

Welding work

Inflowing medium

Measuring range