beautypg.com

VEGA VEGAFLEX 86 4 … 20 mA_HART - four-wire Coax probe User Manual

Page 50

background image

50

7 Setup with PACTware

VEGAFLEX 86 • 4 … 20 mA/HART - four-wire

42285-EN-130314

Information:

In special cases you can change the medium type. This setting can be

changed under "Extended adjustment".
Application

In this field you can select the application you want to use your instru-

ment for. You have the following selection options:

Level in the vessel

Level in the bypass/standpipe

Interface in the vessel

Interface in the bypass/standpipe

Demonstration mode

Level measurement: If you select "Level", you can select the proper-

ties of the medium in another field.
Interface measurement: If you select "Interface", the instrument needs

more information, such as the distance to the interface, the dielectric

constant of the upper medium or whether or not there is a superim-

posed gas phase.
Demonstration mode: This mode is suitable for test and demonstra-

tion purposes. In this mode, the sensor ignores all logic parameters

and reacts immediately to all measured value changes within the

measuring range.
Application - Level measurement

The level measurement refers to the product surface which is the limit

to the gas phase.

Liquids

– Solvents, oils, LPG - dielectric constant < 3

– Chemical mixtures - dielectric constant 3 … 10

– Water-based - dielectric constant > 10

Bulk solids

– Dusts, wood chips - dielectric constant < 1.5

– Granules, dusts, powders - dielectric constant 1.5 … 3

– Cereals, flour - dielectric constant > 3

Application - Interface measurement

The interface measurement refers to the phase limit between two

liquids. The total level is also available as a measured value.

Superimposed gas phase present

– Check if there is a superimposed gas phase in the vessel. This

is always the case if the total level never touches the process

fitting.

Properties

– Here you can enter the dielectric constant of the upper medium

– As an alternative you can enter the distance to the interface

Adjustment for the level measurement

If you have selected level measurement in the previous menu, then

you can enter the values for the min. and max. adjustment. The value

to be entered refers to the distance from the sealing surface of the

process fitting (sensor reference plane) to the surface of the product.

Step 3 of 7

Adjustment