2 protocol description, 2 parameters for the bus communication, The vegapuls 62 is preset with the default values – VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual
Page 67: Start bits and data bits cannot be modified

67
10 Supplement
VEGAPULS 62 • Modbus and Levelmaster protocol
41362-EN-121011
twisted two-wire cable can be up to 1200 m. The bus must be terminated on both sides at the last
bus participant with a terminating resistor of 120 Ohm. The resistor is already integrated in the
VEGAPULS 62 and is activated/deactivated via a slide switch.
4
1
3
3
3
2
+
+
power supply
MODBUS
D0
D1
IS GND
USB
+
+
power supply
MODBUS
D0
D1
IS GND
USB
+
+
power supply
MODBUS
D0
D1
IS GND
USB
1
3 4 5
2
off on
( )
(
)
(-)
(-)
1
3 4 5
2
off on
( )
(
)
(-)
(-)
1
3 4 5
2
off on
( )
(
)
(-)
(-)
Fig. 54: Bus architecture Modbus
1 RTU
2 Connection resistor
3 Bus participant
4 Voltage supply
10.2 Protocol description
The VEGAPULS 62 is suitable for connection to the following RTUs with Modbus RTU or ASCII
protocol.
RTU
Protocol
ABB Totalflow
Modbus RTU, ASCII
Bristol ControlWaveMicro
Modbus RTU, ASCII
Fisher ROC
Modbus RTU, ASCII
ScadaPack
Modbus RTU, ASCII
Thermo Electron Autopilot
Modbus RTU, ASCII
10.2 Parameters for the bus communication
The VEGAPULS 62 is preset with the default values:
Parameter
Configurable Values
Default Value
Baud Rate
1200, 2400, 4800, 9600, 19200
9600
Start Bits
1
1
Data Bits
7, 8
8
Parity
None, Odd, Even
None
Stop Bits
1, 2
1
Address range Modbus
1 … 255
246
Start bits and data bits cannot be modified.