6 Set up the sensor with the indicating and adjustment module

VEGAPULS 62 • Modbus and Levelmaster protocol

41362-EN-121011

Adjustment for all applications which are not typically level meas-

urement

Sensor accepts all measured value changes within the measuring

range immediately

Typical applications:

– Instrument demonstration

– Object recognition/monitoring (additional settings required)

Through this selection, the sensor is adapted optimally to the applica-

tion or the location and measurement reliability under the various

basic conditions is increased considerably.
Enter the requested parameters via the appropriate keys, save your

settings with [OK] and jump to the next menu item with the [ESC] and

the [->] key.

With this selection, the operating range of the sensor is adapted to

the vessel height and the reliability with different frame conditions is

increased considerably.
Independent from this, the min. adjustment must be carried out.

Enter the requested parameters via the appropriate keys, save your

settings with [OK] and jump to the next menu item with the [ESC] and

the [->] key.

Also the vessel form can influence the measurement apart from the

medium and the application. To adapt the sensor to these measure-

ment conditions, this menu item offers you different options for vessel

bottom and ceiling in case of certain applications.

Enter the requested parameters via the appropriate keys, save your

settings with [OK] and jump to the next menu item with the [ESC] and

the [->] key.

Since a radar sensor is a distance measuring instrument, the distance

from the sensor to the product surface is measured. For indication of

the real level, an allocation of the measured distance to the percent-

age height must be carried out.
To perform the adjustment, enter the distance with full and empty ves-

sel, see the following example:

Setup/Vessel height,

measuring range

Setup/Vessel form

Setup/Adjustment