9 Diagnosis, asset management and service

VEGABAR 82 • 4 … 20 mA/HART

45028-EN-131010

F

T

: Thermal change of zero signal and output span

F

Kl

: Deviation

F

a

: Thermal change of the current output

You can find the specifications in chapter "Technical data".

Pressure measurement in the pipeline 8 bar (800 KPa)
Product temperature up to 50 °C
VEGABAR 82 with measuring range 10 bar, deviation < 0.075 %
Calculation of the turn down: TD = 10 bar/8 bar, TD = 1.25
1. step: Calculation of the basic accuracy

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

)

F

T

= (0.15 %) x (0.5 + 0.5 x TD)

F

Kl

= 0.075 %

F

perf

= √((0.15 %) x (0.5 + 0.5 x TD)

2

+ (0.075 %)

2

)

F

perf

= 0.19 %

Step 2: Calculation of the total deviation

F

total

= F

perf

+ F

stab

F

stab

= (0.05 % x TD)

F

stab

= (0.05 % x 1.25)

F

stab

= 0.06 %

F

total

= 0.19 % + 0.063 % = 0.25 %

1. step: Calculation of the basic accuracy

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

+ (F

a

)

2

)

F

T

= (0.15 %) x (0.5 + 0.5 x TD)

F

Kl

= 0.075 %

F

a

= 0.15 %

F

perf

= √((0.15 %) x (0.5 + 0.5 x TD)

2

+ (0.075 %)

2

) + (0.15 %)

2

)

F

perf

= 0.24 %

Step 2: Calculation of the total deviation

F

total

= F

perf

+ F

stab

F

stab

= (0.05 % x TD)

F

stab

= (0.05 % x 1.25)

F

stab

= 0.06 %

F

total

= 0.24 % + 0.06 % = 0.30 %

9.6 Exchange process assembly with version

IP 68 (25 bar)

With version IP 68 (25 bar), the user can exchange the process as-

sembly on site. Connection cable and external housing can be kept.
Required tools:

Hexagon socket wrench, size 2

Practical example

Calculation - Digital out-

put signal

Calculation - Analogue