beautypg.com

VEGA VEGAFLEX 83 Foundation Fieldbus Polished version User Manual

Page 13

background image

13

3 Product description

VEGAFLEX 83 • Foundation Fieldbus

44224-EN-130910

TS

d1

h1

h2

d2

1

L2

L1

L3

Fig. 6: Interface measurement
1 Sensor reference plane (seal surface of the process fitting)

d1 Distance to the interface

d2 Distance to the level

TS Thickness of the upper medium (d1 - d2)

h1 Height - Interface

h2 Height - Level

L1 Lower medium

L2 Upper medium

L3 Gas phase

Upper medium (L2)

The upper medium must not be conductive

The dielectric constant of the upper medium or the actual distance

to the interface must be known (input required). Min. dielectric con-

stant: 1.6. You can find a list of dielectric constants on our home

page: www.vega.com.

The composition of the upper medium must be stable, no varying

products or mixtures

The upper medium must be homogeneous, no stratifications

within the medium

Min. thickness of the upper medium 50 mm (1.97 in)

Clear separation from the lower medium, emulsion phase or detri-

tus layer max. 50 mm (1.97 in)

If possible, no foam on the surface

Lower medium (L1)

The dielectric constant must be 10 higher than the dielectric

constant of the upper medium, preferably electrically conductive.

Example: upper medium dielectric constant 2, lower medium at

least dielectric constant 12.

Gas phase (L3)

Air or gas mixture

Gas phase - dependent on the application, gas pahse does not

always exist (d2 = 0)

Prerequisites for inter-

face measurement