VEGA VEGAFLEX 83 4 … 20 mA_HART two-wire PFA insulated User Manual
Page 51
51
6 Set up with the display and adjustment module
VEGAFLEX 83 • 4 … 20 mA/HART two-wire
41834-EN-130612
Menu item
Default value
Modified value
Medium, dielectric constant
Water-based, > 10
Superimposed gas phase
Yes
Dielectric figure, upper medium (TS)
1.5
Tube inner diameter
200 mm
Max. adjustment - Level
100 %
Max. adjustment - Level
Distance: 0.000 m(d) - note block-
ing distances
Min. adjustment - Level
0 %
Min. adjustment - Level
Distance: Probe length - take dead
band into account
Accept adjustment of the level measurement?
Yes
Max. adjustment - Interface
100 %
Max. adjustment - Interface
Distance: 0.000 m(d) - note block-
ing distances
Min. adjustment - Interface
0 %
Min. adjustment - Interface
Distance: Probe length - take dead
band into account
Integration time - Level
0.0 s
Integration time - Interface
0.0 s
Linearization type
Linear
Linearization - Socket correction
0 mm
Linearization - Vessel height
Probe length
Scaling size - Level
Volume in l
Scaling unit - Level
Litres
Scaling format - Level
Without decimal positions
Scaling level - 100 % correspond to
100
Scaling level - 0 % correspond to
0
Accept scaling of the level measurement
Yes
Scaling variable - Interface
Volume
Scaling unit - Interface
Litres
Scaling format - Interface
Without decimal positions
Scaling interface - 100 % correspond to
100
Scaling interface - 0 % correspond to
0
Current output, output variable
First HART variable (PV)
Lin. percent - Level
Current output - Output characteristics
0 … 100 % correspond to
4 … 20 mA
Current output - Reaction in case of failure
≤ 3.6 mA
Current output - Min.
3.8 mA