8 Diagnosis, asset management and service
VEGABAR 82 • 4 … 20 mA
45027-EN-131010
•
F
T
: Thermal change of zero signal and output span
•
F
Kl
: Deviation
•
F
a
: Thermal change of the current output
You can find the specifications in chapter "Technical data".
Pressure measurement in the pipeline 8 bar (800 KPa)
Product temperature up to 50 °C
VEGABAR 82 with measuring range 10 bar, deviation < 0.075 %
Calculation of the set Turn Down: TD = 10 bar/8 bar, TD = 1.25
1. step: Calculation of the basic accuracy
F
perf
= √((F
T
)
2
+ (F
Kl
)
2
+ (F
a
)
2
)
F
T
= (0.15 %) x (0.5 + 0.5 x TD)
F
Kl
= 0.075 %
F
a
= 0.15 %
F
perf
= √((0.15 %) x (0.5 + 0.5 x TD)
2
+ (0.075 %)
2
) + (0.15 %)
2
)
F
perf
= 0.24 %
Step 2: Calculation of the total deviation
F
total
= F
perf
+ F
stab
F
stab
= (0.05 % x TD)/year
F
stab
= (0.05 % x 1.25)/year
F
stab
= 0.06 %
F
total
= 0.24 % + 0.06 % = 0.30 %
8.6 Exchange process assembly with version
IP 68 (25 bar)
With version IP 68 (25 bar), the user can exchange the process as-
sembly on site. Connection cable and external housing can be kept.
Required tools:
•
Hexagon socket wrench, size 2
Caution:
The exchange may only be carried out in the complete absence of
line voltage.
In Ex applications, only a replacement part with appropriate Ex ap-
proval may be used.
Proceed as follows when carrying out the exchange:
1. Losen the fixing screw with the hexagon socket wrench
2. Carefully detach the cable assembly from the process assembly
Practical example
Calculation