25
6 Set up with the display and adjustment module
VEGABAR 87 • Slave sensor for electronic differential pressure
45053-EN-131011
6 Set up with the display and adjustment
module
6.1 Parameter adjustment - Quick setup
To quickly and easily adapt the sensor to the application, select
the menu item "Quick setup" in the start graphic on the display and
adjustment module.
Carry out the following steps in the sequence specified below. The
presettings apply to all applications.
You can find "Extended adjustment" in the next sub-chapter.
1. Measurement loop name
In the first menu item you assign a suitable measurement loop name.
Permitted are names with max. 19 characters.
2. Application
In this menu item you activate/deactivate the slave sensor for elec-
tronic differential pressure and select the application.
Note:
It is absolutely necessary to activate the slave sensor in advance to
have the applications displayed in the electronic differential pressure
measurement menus.
3. Units
In this menu item you determine the adjustment and temperature
units of the instrument. Depending on the selected application in the
menu item "Application", different adjustment units are available.
4. Unit, static pressure
In this menu item, you determine the unit of the static, i.e. superim-
posed pressure.
5. Position correction
In this menu item you compensate the influence of the installation
position of the instrument (offset) to the measured value.
6. Min. adjustment
In this menu item you carry out the min. adjustment for level.
Enter the percentage value and the corresponding pressure value for
the min. level.
7. Max. adjustment
In this menu item you carry out the max. adjustment for level.
Presettings
Quick setup - Level meas-
urement