VEGA VEGABAR 66 4 … 20 mA_HART User Manual
Page 62
62
10 Supplement
VEGABAR 66 • 4 ... 20 mA/HART
36737-EN-130321
Material
Ʋ Housing
ABS
Ʋ Inspection window
Polyester foil
Voltage supply
Operating voltage
Ʋ Non-Ex instrument
12 … 36 V DC
Ʋ Ex-ia instrument
12 … 30 V DC
Ʋ Exd instrument
18 … 36 V DC
Operating voltage with illuminated display and adjustment module
Ʋ Non-Ex instrument
20 … 36 V DC
Ʋ Ex-ia instrument
20 … 30 V DC
Ʋ Ex d instrument
20 … 36 V DC
Permissible residual ripple
Ʋ < 100 Hz
U
ss
< 1 V
Ʋ 100 Hz … 10 kHz
U
ss
< 10 mV
Load
see diagram
1000
750
500
250
12
18
16
14
20
22
24
26
28
30
32
34
36
Ω
V
4
1
2
3
Fig. 34: Voltage diagram
1 HART load
2 Voltage limit Ex-ia instrument
3 Voltage limit non-Ex/Ex-d instrument
4 Operating voltage
Electrical protective measures
Protection rating
Ʋ Transmitter
IP 68 (25 bar)
Ʋ Housing, standard
IP 66/IP 67
21)
Ʋ Aluminium and stainless housing
(optionally available)
IP 68 (1 bar)
22)
Ʋ External housing
IP 65
Overvoltage category
III
21)
Instruments with gauge pressure measuring ranges cannot detect the ambient pressure when submerged, e.g.
in water. This can lead to falsification of the measured value.
22)
Only with instruments with absolute pressure ranges.