10 Supplement
VEGABAR 66 • 4 ... 20 mA/HART
36737-EN-130321
Nominal range
Overload capacity, max.
pressure
Overload capacity, min. pres-
sure
0 … 1 bar/0 … 100 kPa
35 bar/3500 kPa
0 bar abs.
0 … 2.5 bar/0 … 250 kPa
50 bar/5000 kPa
0 bar abs.
0 … 5 bar/0 … 500 kPa
65 bar/6500 kPa
0 bar abs.
0 … 10 bar/0 … 1000 kPa
90 bar/9000 kPa
0 bar abs.
0 … 25 bar/0 … 2500 kPa
130 bar/13000 kPa
0 bar abs.
Nominal measuring ranges and overload capability in psig
The specifications are only an overview and refer to the measuring cell. Limitations due to the ma-
terial and version of the process fitting are possible. The specifications on the nameplate apply.
Nominal range
Overload capacity, max.
pressure
Overload capacity, min. pres-
sure
Gauge pressure
0 … +1.5 psig
+200 psig
-3 psig
0 … +3 psig
+290 psig
-6 psig
0 … +6 psig
+430 psig
-12 psig
0 … +15 psig
+500 psig
-15 psig
0 … +35 psig
+700 psig
-15 psig
0 … +70 psig
+950 psig
-15 psig
0 … +150 psig
+1300 psig
-15 psig
0 … +350 psig
+1900 psig
-15 psig
0 … +900 psig
+2900 psig
-15 psig
Absolute pressure
0 … 15 psi
500 psi
0 psi
0 … 35 psi
700 psi
0 psi
0 … 70 psi
900 psi
0 psi
0 … 150 psi
1300 psi
0 psi
0 … 350 psi
1900 psi
0 psi
Reference conditions and actuating variables (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1
Ʋ Temperature
+15 … +25 °C (+59 … +77 °F)
Ʋ Relative humidity
45 … 75 %
Ʋ Air pressure
860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)
Determination of characteristics
Limit point adjustment according to IEC 61298-2
Characterstic curve
Linear
Reference installation position
upright, diaphragm points downward
Influence of the installation position
< 0.2 mbar/20 Pa (0.003 psig)