A metallic measuring cell is used as sensor element. The process

pressures are transmitted via the separating diaphragms and filling

oils to a resistance measuring bridge (semi-conductor technology).
The difference between the acting pressures generates a change in

the bridge voltage. This change is measured, further processed and

converted into a corresponding output signal.
The markings "+" and "-" on the process component in chapter

"Mounting and connection instructions" must therefore be noted when

connecting to the process. The pressure acting on "+" goes positive,

the pressure acting on "-" goes negative into the calculation of the

pressure difference.
The configuration of the measuring cells differs depending on the

measuring range:

1
2

3

4

5

1

p

2

p

Fig. 8: Metallic measuring cell 10 mbar and 30 mbar - p

1

and p

2

process pres-

sures
1 Measuring element

2 Silicone diaphragm

3 Separating diaphragm

4 Filling oil

5 Integrated overvoltage arrester

1

p

2

p

1

2

3

4

Fig. 9: Metallic measuring cell from 100 mbar - p

1

and p

2

process pressures

1 Measuring element

2 Overload diaphragm/Middle diaphragm

3 Filling oil

4 Separating diaphragm

4 … 20 mA two-wire electronics for voltage supply and measured

value transmission on the same cable.
The supply voltage range can differ depending on the instrument ver-

sion. The exact range is stated in chapter "Technical data".
The backlight of the display and adjustment module is powered by

the sensor. The prerequisite for this is a supply voltage at a certain

Functional principle

Voltage supply