beautypg.com

VEGA VEGAPULS 67 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA User Manual

Page 17

background image

17

4 Mounting

VEGAPULS 67 • Profibus PA

36533-EN-121011

Mount the instrument at least 200 mm (7.874 in) away from the vessel

wall.

200 mm

(7.87")

Fig. 10: Mounting of the radar sensor on the vessel top

If you cannot keep this distance you should carry out a false echo

storage before setup. This applies mainly if buildup on the vessel wall

is expected. In this case, we recommend repeating a false echo stor-

age later with existing buildup.

Filling from the top: Mounting should not be too close to the inflow-

ing material as the microwave signal will be interferred. The optimum

mounting position is on the opposite of the filling. To avoid strong

pollution, the distance to the filter or dust extraction must be as big as

possible.

Fig. 11: Mounting of the radar sensor with inflowing medium with filling from the

top

Lateral filling: With bulk solids silos with lateral pneumatic filling,

mounting should not be in the filling stream as the microwave signal

will be interferred. The optimum mounting position is next to the filling.

To avoid strong pollution, the distance to the filter or dust extraction

must be as big as possible.

Installation position

Inflowing medium