3 wiring plan, double chamber housing – VEGA VEGAPULS 66 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART - four-wire User Manual
Page 25
25
5 Connecting to power supply
VEGAPULS 66 • 4 … 20 mA/HART - four-wire
36520-EN-121011
Fig. 17: Connection steps 5 and 6
6. Insert the wire ends into the terminals according to the wiring plan
Information:
Solid cores as well as flexible cores with cable end sleeves are
inserted directly into the terminal openings. In case of flexible cores
without end sleeves, press the terminal head with a small screwdriver;
the terminal opening is freed. When the screwdriver is released, the
terminal closes again.
You can find further information to the max. wire cross-section under
"Technical data/Electromechanical data"
7. Check the hold of the wires in the terminals by lightly pulling on
them
8. Connect the screen to the internal ground terminal, connect the
outer ground terminal to potential equalisation
9. Tighten the compression nut of the cable entry. The seal ring must
completely encircle the cable
10. Place probably existing indicating and adjustment module back
on
11. Screw the housing cover back on
The electrical connection is hence finished.
5.3 Wiring plan, double chamber housing
The following illustrations apply to the non-Ex as well as to the Ex-d
version.