beautypg.com

Quick start – VEGA VEGAPULS 66 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART - four-wire User Manual

Page 2

background image

2

Quick start

VEGAPULS 66 • 4 … 20 mA/HART - four-wire

36520-EN-121011

Quick start

The quick start enables a quick setup with many applications. You

can find further information in the respective chapters of the operating

instructions manual.
1. Distance from the vessel wall > 200 mm, the antenna should

protrude > 10 mm into the vessel

> 500 mm

(19.69")

ca. 10 mm

Fig. 1: Distance of the antenna to the vessel wall/vessel ceiling

2. Note min. socket diameter depending on the socket length
For further information see chapter "Mounting".
1. Make sure that the power supply corresponds to the specifica-

tions on the type label.

2. Connect the instrument according to the following illustration

power supply

4...20mA

active

passive

common

IS GND

5

1

/L

/N

PE

2

+

( )

(-)

6 7

8

Fig. 2: Connection compartment with double chamber housing with mains

voltage

For further information see chapter "Connecting to power supply".
1. Go via the indicating and adjustment module to the menu "Setup".

2. In the menu item "Medium"you select the medium of your applica-

tion, for example "Aqueous solution".

3. Select in the menu item "Application" the vessel, the application

and the vessel form, for example, storage tank.

Mounting

Connect electrically

Set parameters