10 Supplement

VEGABAR 67 • 4 ... 20 mA/HART - climate compensated

39444-EN-130321

Weight approx.

Ʋ Basic weight

0.7 kg (1.543 lbs)

Ʋ Suspension cable

0.1 kg/m (0.07 lbs/ft)

Ʋ Connection tube

1.5 kg/m (1 lbs/ft)

Ʋ Straining clamp

0.2 kg (0.441 lbs)

Ʋ Threaded fitting

0.4 kg (0.882 lbs)

Lengths

Ʋ Connection tube

0.25 … 6 m (0.82 … 19.69 ft)

Output variable
Output signal

4 … 20 mA/HART

HART output values according to HART standard 5.0

Ʋ Primary Value

Pressure

Ʋ Secondary Value

Temperature

10)

Signal resolution

1.6 µA

Failure signal current output (adjustable) mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA
Max. output current

22 mA

Load

see load diagram under Power supply

Met NAMUR recommendation

NE 43

Dynamic behaviour output
Run-up time approx.

10 s

90 %

100 %

10 %

t

t

T

A

t

t

S

2

1

Fig. 32: Sudden change of the process variable. t

T

: dead time; t

A

: rise time; t

S

: jump response time

1 Process variable

2 Output signal

Dead time

≤ 150 ms

Rise time

≤ 100 ms (10 … 90 %)

Step response time

≤ 250 ms (ti: 0 s, 10 … 90 %)

Damping (63 % of the input variable)

0 … 999 s, adjustable

10)

Depending on the respective instrument and the process fitting, the temperature can deviate from the real

process temperature.