VEGA VEGABAR 67 4 … 20 mA_HART - climate compensated User Manual
Page 38
38
6 Set up with the display and adjustment module PLICSCOM
VEGABAR 67 • 4 ... 20 mA/HART - climate compensated
39444-EN-130321
Unit
Unit of measurement
bar
▼
Temperature unit
°C
▼
3. Activate the selection with [OK] and select "Units of measure-
ment with [->].
4. Activate the selection with [OK] and select the requested unit with
[->] (in the example mbar).
5. Confirm with [OK] and move to position correction with [->].
The adjustment unit is thus switched over from bar to mbar.
Proceed as follows to select the temperature unit:
6)
1. Activate the selection with [OK] and select "Temperature unit
with [->].
2. Activate the selection with [OK] and select the requested unit with
[->] (e.g. °F).
3. Confirm with [OK].
The temperature unit is hence switched over from °C to °F.
Proceed as follows:
1. Activate in the menu item "Position correction" the selection with
[OK].
Position correction
Offset
P
=
+0000 mbar
53 mbar
2. Select with [->], e.g. to accept actual measured value.
Position correction
Accept current measured
value?
▶
Accept
Edit
3. Confirm with [OK] and move to min.(zero) adjustment with [->].
Proceed as follows:
1. Edit the mbar value in the menu item "zero" with [OK].
Zero
000.0 %
P
=
+0000.0 mbar
0000.0 mbar
2. Set the requested mbar value with [+] and [->].
3. Confirm with [+] and move to span adjustment with [->].
The zero adjustment is finished.
Carry out a position cor-
rection
Carrying out zero adjust-
ment
6)
Selection options: °C, °F.