10 Supplement
VEGABAR 54 • 4 … 20 mA/HART
36726-EN-130321
Protection rating
Ʋ unassembled
IP 20
Ʋ mounted into the sensor without cover IP 40
Material
Ʋ Housing
ABS
Ʋ Inspection window
Polyester foil
Voltage supply
Operating voltage
Ʋ Non-Ex instrument
12 … 36 V DC
Ʋ EEx-ia instrument
12 … 30 V DC
Operating voltage with illuminated display and adjustment module
Ʋ Non-Ex instrument
20 … 36 V DC
Ʋ EEx-ia instrument
20 … 30 V DC
Permissible residual ripple
Ʋ < 100 Hz
U
ss
< 1 V
Ʋ 100 Hz … 10 kHz
U
ss
< 10 mV
Load
see diagram
1000
750
500
250
12
18
16
14
20
22
24
26
28
30
32
34
36
Ω
V
4
1
2
3
Fig. 26: Voltage diagram
1 HART load with HART version
2 Voltage limit EEx-ia instrument
3 Voltage limit non-Ex instrument
4 Operating voltage
Electrical protective measures
Protection rating
Ʋ Housing, standard
IP 66/IP 67
16)
Ʋ Aluminium and stainless housing
(optionally available)
IP 68 (1 bar)
17)
Ʋ Process component in IP 68 version IP 68 (25 bar)
Ʋ External housing
IP 65, IP 66/IP 68 (0.2 bar)
16)
Instruments with gauge pressure measuring ranges cannot detect the ambient pressure when submerged, e.g.
in water. This can lead to falsification of the measured value.
17)
Only with instruments with absolute pressure ranges.