4 switch-on phase – VEGA VEGAPULS 66 (≥ 2.0.0 - ≥ 4.0.0) standpipe ver. 4 … 20 mA_HART - four-wire User Manual
Page 18
18
5 Connecting to power supply
VEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire
36524-EN-121011
power supply
4...20mA
active
passive
common
IS GND
5
1
/L
/N
2
+
( )
(-)
6 7
8
Fig. 6: Connection compartment with double chamber housing with low voltage
Terminal
Function
Polarity
1
Voltage supply
+/L
2
Voltage supply
-/N
5
4 … 20 mA output (active)
+
6
4 … 20 mA output (passive)
+
7
Mass - output
-
8
Function ground with installa-
tion according to CSA
5.4 Switch-on phase
After connecting the instrument to power supply or after a voltage
recurrence, the instrument carries out a self-check for approx. 30 s:
•
Internal check of the electronics
•
Indication of the instrument type, hardware and software version,
measurement loop name on the display or PC
•
Indication of the status message "F 105 Determine measured
value" on the display or PC
•
The output signal jumps to the set error current
As soon as a plausible measured value is found, the corresponding
current is outputted to the signal cable. The value corresponds to the
actual level as well as the settings already carried out, e.g. factory
setting.
Connection compartment
with low voltage