4 setup steps – VEGA VEGABAR 52 Profibus PA - climate compensated User Manual
Page 28
28
6 Set up with the display and adjustment module PLICSCOM
VEGABAR 52 • Profibus PA - climate compensated
36788-EN-130321
– Save value
•
[->] key to select:
– Menu change
– Select list entry
– Select editing position
•
[+] key:
– Change value of the parameter
•
[ESC] key:
– interrupt input
– Jump to next higher menu
The sensor is adjusted via the four keys of the display and adjust-
ment module. The LC display indicates the individual menu items. The
functions of the individual keys are shown in the above illustration.
Approx. 10 minutes after the last pressing of a key, an automatic reset
to measured value indication is triggered. Any values not confirmed
with [OK] will not be saved.
6.4 Setup steps
Before starting the actual parameter adjustment of a Profibus PA
sensor, the address setting must first be carried out. You will find a
detailed description in the operating instructions manual of the display
and adjustment module or in the online help of PACTware or DTM.
VEGABAR 52 can be used for level as well as for process pressure
measurement. Default setting is level measurement. The mode can be
changed in the adjustment menu.
Depending on the application only the respective subchapter "Level
or process pressure measurement" is of importance. There, you find
the individual adjustment steps.
Level measurement
Set up VEGABAR 52 in the following sequence:
1. Selecting adjustment unit/density unit
2. Carry out a position correction
3. Carry out min. adjustment
4. Carry out max. adjustment
In the menu item "Adjustment unit" you select the physical unit in
which the adjustment should be carried out, e.g. mbar, bar, psi…
The position correction compensates the influence of the mounting
position or static pressure on the measurement. It does not influence
the adjustment values.
Information:
The steps 1, 3 and 4 are not necessary for instruments which are
already preset according to customer specifications!
You can find the data on the type label on the instrument or in the
menu items of the min./max. adjustment.
Adjustment system
Address setting
Level or process pres-
sure measurement
Parameter adjustment
"Level measurement"