beautypg.com

VEGA VEGABAR 66 Foundation Fieldbus - climate compensated User Manual

Page 62

background image

62

10 Supplement

VEGABAR 66 • Foundation Fieldbus - climate compensated

36793-EN-130321

secondary_value_2

– Value after min/max-adjustment. Selected as input to AIFB by setting 'Channel' = 3. Unit

derives from 'Secondary_value_2_unit'

secondary_value_2_unit

– Selected unit code for "secondary_value_2"

sensor_value

– Raw sensor value, i.e. the uncalibrated measurement value from the sensor. Unit derives from

'Sensor_range.unit'

sensor_range

– "Sensor_range.unit' refers to 'Sensor_value', 'Max/Min_peak_sensor_value', 'Cal_point_hi/lo'

– includes sensor unit: bar, PSI …; only unit part of DS-68 is writable

simulate_primary_value

simulate_secondary_value_1

simulate_secondary_value_2

device status

– "0: ""OK"" 13: ""non-specific error"" 17: ""Cal span too small"" 34: ""EEPROM memory fault""

36: ""ROM memory fault"" 37: ""RAM memory fault"" 40: ""non-specific hardware fault"" 41:

""Sensor element not found"" 42: ""No leaking pulse"" 43: ""No trigger signal"" 44: ""EMI error""

113: ""Communication hardware fault"""

linearization type

– Possible types of linearization are: linear, user defined, cylindrical lying container, spherical

container

– "0: ""Linear"" 1: ""User def"" 20: ""Cylindrical lying container"" 21: ""Spherical container"""

curve_points_1_10

– X and Y values for the user defined linearization curve

curve_points_11_20

– X and Y values for the user defined linearization curve

curve_points_21_30

– X and Y values for the user defined linearization curve

curve_points_31_33

– X and Y values for the user defined linearization curve

curve status

– Result of table plausibility check

– "0: ""Uninitialized"" 1: ""Good"" 2: ""Not monotonous increasing"" 3: ""Not monotonous

decreasing"" 4: ""Not enough values transmitted"" 5: ""Too many values transmitted"" 6: ""Gra-

dient of edge too high"" 7: ""Values not excepted"" 8: ""Table currently loaded"" 9: ""Sorting and

checking table"""

SUB_DEVICE_NUMBER

SENSOR_ELEMENT_TYPE

– 0: "non-specific"

display_source_selector

– Selects the type of value that is displayed on the indication-/adjustement-module

– "0: ""Physical value"" 1: ""Percent value"" 2: ""Lin percent value"" 6: ""Out(AI1)"" 7: ""Level"" 8:

""Out(AI2)"" 9: ""Out(AI3)"""

max_peak_sensor_value

– Holds the maximum sensor value. Write access resets to current value. Unit derives from 'Sen-

sor_range.unit'

– Write access resets to current value

min_peak_sensor_value

– Holds the minimum sensor value. Write access resets to current value. Unit derives from 'Sen-

sor_range.unit'

– Write access resets to current value

CAL_POINT_HI