4 Mounting

VEGABAR 66 • Foundation Fieldbus - climate compensated

36793-EN-130321

2

1

2

1

2

1

1

2

Fig. 4: Position of the filter element
1 Filter element

2 Blind plug

Caution:

Due to the filter effect, the pressure compensation is time delayed.

When opening/closing the housing cover quickly, the measured value

can change for a period of approx. 5 s by up to 15 mbar.
Information:

Make sure that the filter element is always free of buildup during

operation. A high-pressure cleaner may not be used for cleaning.
With instrument versions in protection IP 66/IP 68, 1 bar, the ventila-

tion is realised via the capillaries in the permanently connected cable.

The filter element is replaced by a blind plug.

4.2 Mounting preparations

For the suspension cable version note the following points when

selecting the mounting position:

Sideways movements of the transmitter can cause measurement

errors

1. Therefore, mount VEGABAR 66 in a calm area or in a suitable

protective tube

The suspension cable has a capillary for atmospheric pressure

compensation

2. Therefore lead the cable end into a dry space or directly to the

external electronics

The external electronics is provided with terminals and a filter element

for pressure compensation. Keep in mind for all versions:

The protective cover prevents mechanical damage to the measur-

ing cell. It should only be removed when the sensor is deployed in

extremely polluted water.