3 Product description

VEGABAR 54 • Profibus PA - climate compensated

36790-EN-130321

signal, compared with an integrated reference pressure measurement

and outputted as measured value via the output signal.
The CERTEC

®

measuring cell is also equipped with a temperature

sensor. The temperature value can be displayed via the display and

adjustment module or processed via the signal output.

As a standard feature, the CERTEC

®

measuring cell is equipped with

a lateral, recessed seal.
Instruments with double seal have an additional front seal.
Instruments with hygienic fitting are equipped with a gap-free form

seal.

Power supply via the Profibus DP/PA segment coupler or VEGALOG

571 EP cards. A two-wire cable according to Profibus specification

serves as carrier of both power and digital data transmission for

multiple sensors. The instrument profile of VEGABAR 54 corresponds

to profile specification version 3.0.
The backlight of the display and adjustment module is powered by the

sensor. Prerequisite is a certain level of operating voltage.
The data for power supply are specified in chapter "Technical data".
The optional heating requires its own operating voltage. You can find

details in the supplementary instructions manual "Heating for display

and adjustment module".
This function is generally not available for approved instruments.

The GSD (instrument master files) and bitmap files necessary for

planning your Profibus-DP-(PA) communication network are available

from the download section on the VEGA homepage www.vega.com

under "Services - Downloads - Software - Profibus". There you can

also find the appropriate certificates. In a PDM environment, an EDD

(Electronic Device Description) is also required to enable the full

range of sensor functions (also available as a download).A CD with

the appropriate files can be ordered via e-mail under [email protected].

com or by phone from one of the VEGA agencies under the order

number "DRIVER.S".

3.3 Operation

The instrument can be adjusted with the following adjustment media:

With the display and adjustment module

with the suitable VEGA DTM in conjunction with an adjustment

software according to the FDT/DTM standard, e.g. PACTware and

PC

with the adjustment program PDM

3.4 Packaging, transport and storage

Your instrument was protected by packaging during transport. Its

capacity to handle normal loads during transport is assured by a test

based on ISO 4180.

Seal concept

Power supply and bus

communication

GSD/EDD

Packaging