10 Supplement

VEGABAR 54 • Profibus PA - climate compensated

36790-EN-130321

Status

code

Description according to

Profibus standard

Possible cause

0 x 04

bad - configuration error

– Adjustment error

– Configuration error with PV-Scale (PV-Span too small)

– Unit irregularity

– Error in the linearization table

0 x 0C

bad - sensor failure

– Hardware error

– Converter error

– Leakage pulse error

– Trigger error

0 x 10

bad - sensor failure

– Measured value generation error

– Temperature measurement error

0 x 1f

bad - out of service constant

"Out of Service" mode switched on

0 x 44

uncertain - last unstable value

Failsafe replacement value (Failsafe-Mode = "Last value" and al-

ready valid measured value since switching on)

0 x 48

uncertain substitute set

– Switch on simulation

– Failsafe replacement value (Failsafe-Mode = "Fsafe value")

0 x 4c

uncertain - initial value

Failsafe replacement value (Failsafe-Mode = "Last valid value" and

no valid measured value since switching on)

0 x 51

uncertain - sensor; conversion

not accurate - low limited

Sensor value < lower limit

0 x 52

uncertain - sensor; conversion

not accurate - high limited

Sensor value > upper limit

0 x 80

good (non-cascade) - OK

OK

0 x 84

good (non-cascade) - active

block alarm

Static revision (FB, TB) changed (10 sec. active, after the parame-

ter of the static category has been written)

0 x 89

good (non-cascade) - active ad-

visory alarm - low limited

Lo-Alarm

0 x 8a

good (non-cascade) - active ad-

visory alarm - high limited

Hi-Alarm

0 x 8d

good (non-cascade) - active crit-

ical alarm - low limited

Lo-Lo-Alarm

0 x 8e

good (non-cascade) - active crit-

ical alarm - high limited

Hi-Hi-Alarm

10.3 Dimensions

The following dimensional drawings represent only an extract of the possible versions. Detailed

dimensional drawings can be downloaded on www.vega.com under "Downloads" and "Drawings".
The two chamber housings are not available with instruments with 4 … 20 mA signal output