4 saving the parameter adjustment data – VEGA VEGAPULS 68 (≥ 2.0.0 - ≥ 4.0.0) Foundation Fieldbus User Manual
Page 48
48
6 Set up with the indicating and adjustment module
VEGAPULS 68 • Foundation Fieldbus
36538-EN-121011
•
Setup: Resetting of the parameter settings to the default values of
the respective instrument . Order-related settings remain but are
not taken over into the current parameters. User-generated false
signal suppression, user-programmed linearization curve, meas-
ured value memory, echo curve memory as well as event memory
remain untouched. The linearization is set to linear.
•
False signal suppression: Deleting a previously created false
signal suppression. The false signal suppression created in the
factory remains active.
•
Peak values measured value: Resetting of the measured min.
and max. distances to the actual measured value.
Select the requested reset function [->] and confirm with [OK].
The following table shows the default values of VEGAPULS 68:
Menu section
Menu item
Default value
Setup
Measurement
loop name
Sensor
Medium
Liquid/Water
Bulk solids/Crushed stones, gravel
Applications
Storage tank
Silo
Vessel form
Vessel bottom, dished boiler end
Vessel top, dished boiler end
Vesell height/
Measuring range
Recommended measuring range, see
"Technical data" in the supplement
Min. adjustment
Recommended measuring range, see
"Technical data" in the supplement
Damping
0.0 s
Display
Language
Like order
Displayed value
Distance
Display unit
m(d)
Scaling
0.00 %, 0 l
100.00 %, 100 l
Additional adjust-
ments
Distance unit
m
Temperature unit °C
Unit SV2
m
Probe length
Length of the standpipe Ex factory
Linearisation
curve
Linear
6.4 Saving the parameter adjustment data
We recommended noting the adjusted data, e.g. in this operating
instructions manual, and archiving them afterwards. They are thus
available for multiple use or service purposes.