4 Mounting

VEGABAR 51 • Foundation Fieldbus

36715-EN-130321

Instruments in the version "Oil and grease free for oxygen" should

be unpacked just before mounting. After the protective cover of the

process fitting has been removed, the label "O

2

" on the process fitting

is visible.
Danger:

Avoid oil, grease or contamination. Explosion danger!

4.2 Mounting steps

For mounting VEGABAR 51, a welded socket is required. You can find

these components in the supplementary instructions manual "Welded

socket and seals".

Seal the thread with resistant seal material on the process fitting

thread 1½ NPT.

Screw VEGABAR 51 into the welded socket. Tighten the hexagon

on the process fitting with a suitable wrench. Wrench size, see

chapter "Dimensions".

Warning:

The housing must not be used to screw the instrument in! Applying

tightening force can damage internal parts of the housing.

4.3 Mounting steps, tube isolating diaphragm

The isolating systems are temperature and pressure-aged at 80 °C

and 18 bar. The zero point is adjusted at 22 °C ±2 °C and a torque

of 275 Nm. The defined installation position is: Tube chemical seal

horizontal, VEGABAR 51 vertical.
For mounting proceed as follows:
1. Position VEGABAR 51 with tube chemical seal
2. Tighten the threaded fittings step-by-step once on the right and

on the left

3. Hold VEGABAR 51, to avoid distortion from the defined installa-

tion position.

Caution:

Apart from mounting, the tube chemical seal must not be permanently

under torsion.
4. Check current after mounting. The current must be between 3.9

and 4.1 mA. In case of a deviating value, losen threaded fitting

and mount again.

Information:

By slightly increasing or reducing the torque, the current can be set

exactly to 20 mA.

4.4 Mounting steps, external housing

1. Mark the holes according to the following drilling template
2. Depending on the mounting surface, fasten the wall mounting

plate with 4 screws

Oxygen applications

Welding the socket

Sealing/Screwing in

threaded versions