2 prerequisites, 1 authorised personnel, 2 required tools – VEGA VEGAPULS series 60 Recurring function test User Manual
Page 5: 3 required comparative data, 4 required plant situation, 2prerequisites
2
Prerequisites
2
.1 Authorised personnel
All operations described in this operating instructions manual must be
carried out only by trained specialist personnel authorised by the plant
operator.
During work on and with the device the required personal protective
equipment must always be worn.
2
.2 Required tools
l
This test instruction
l
PACTware
l
Actual VEGA DTM Collection
l
Device-DTM of the corresponding sensor (part of the VEGA DTM
Collection)
l
Communication-DTM (part of the VEGA DTM Collection)
l
Interface adapter VEGACONNECT
l
mA-meter or PLC resp. DCS (accuracy ≤±0.2 %)
l
Operating instructions manual of the sensor
l
Safety Manual
2
.3 Required comparative data
The setup data should be used for verification of the settings.
The following setup data are required:
l
Sensor documentation of the setup with all parameters or a sensor
documentation created at least 6 months ago
l
Documentation of all parameter changes since the setup
If the sensor documentation of the setup or a sensor documentation
created at least 6 months ago is not available, then the described
recurring function test (λ
du
96 %) cannot be carried out completely. In
this case, only the test at a detection rate of 88 % of all dangerous,
undetected failures is possible.
2
.4 Required plant situation
Caution:
Make sure that there are no considerable process-relating changes in
your plant during the recurring function test. This means also that the
level in the vessel should not change significantly by filling or emptying
during the test. Make sure that also temperature changes, stirrers,
current reactions in the vessel, etc. can cause level changes.
Recurring function test • for VEGAPULS series 60
5
2 Prerequisites
36553
-
EN
-100225