3 supplementary information foundation fieldbus – VEGA VEGAPULS WL 61 Foundation Fieldbus User Manual
Page 42

42
9 Supplement
VEGAPULS WL 61 • Foundation Fieldbus
38063-EN-121011
Country
Name of the Station
Geographic Latitude
Geographic Longitude
UK
Cambridge
52°09'59" N
00°02'20" E
Darnhall
53°09'22" N
02°32'03" W
Jodrell Bank
53°14'10" N
02°18'26" W
Knockin
52°47'24" N
02°59'45" W
Pickmere
53°17'18" N
02°26'38" W
9.3 Supplementary information Foundation Fieldbus
The following table gives you an overview of the instrument versions and the corresponding device
descriptions, the electrical characteristics of the bus system as well as the applied function blocks.
Revisions Data
DD-Revision
Rev_01
CFF-File
010101.cff
Device Revision
0101.ffo
0101.sym
Cff-Revision
xx xx 01
Device software revision
> 4.4.0
ITK (Interoperability Test Kit) Number
5.0.2
Electricial Characteristics
Physicial Layer Type
Low-power signaling, bus-pow-
ered, FISCO I.S.
Input Impedance
> 3000 Ohms between
7.8 KHz - 39 KHz
Unbalanced Capacitance
< 250 pF to ground from either
input terminal
Output Amplitude
0.8 V P-P
Electrical Connection
2 Wire
Polarity Insensitive
Yes
Max. Current Load
10 mA
Device minimum operating voltage
9 V
Transmitter Function Blocks
Resource Block (RB)
1
Transducer Block (TB)
1
Standard Block (AI)
3
Execution Time
30 mS
Advanced Function Blocks
Discret Input (DI)
Yes
PID Control
Yes
Output Splitter (OS)
Yes
Signal Characterizer (SC)
Yes
Integrator
Yes
Input Selector (IS)
Yes
Arithmetic (AR)
Yes