6 Set up with the indicating and adjustment module

VEGAPULS 68 • Profibus PA

36537-EN-130205

Enter the requested parameters via the appropriate keys, save your

settings and jump to the next menu item with the [ESC] and [->] key.
Caution:

Note the following if the instrument with corresponding approval is

used as part of an overfill protection system according to WHG:
If a linearization curve is selected, the measuring signal is no longer

linearly proportional to the level. This must be taken into consideration

by the user, particularly when setting the switching point on the limit

signal indicator.

When a reset is carried out, all settings (with only a few exceptions)

are reset. The exceptions are: PIN, language, lighting, SIL and HART

mode.

The following reset functions are available:

Delivery status: Restoring the parameter settings at the time

of shipment from the factory incl. the order-specific settings. A

created false signal suppression, user-programmable linearization

curve, measured value memory as well as event memory will be

deleted.

Basic settings: Resetting of the parameter settings incl. special

and laboratory parameters to the default values of the respective

instrument. Any created false signal suppression, user program-

mable linearization curve, measured value memory as well as

event memory will be deleted.

Setup: Resetting of the parameter settings to the default values of

the respective instrument . Order-related settings remain but are

not taken over into the current parameters. User-generated false

signal suppression, user-programmed linearization curve, measu-

red value memory, echo curve memory as well as event memory

remain untouched. The linearization is set to linear.

False signal suppression: Deleting a previously created false

signal suppression. The false signal suppression created in the

factory remains active.

Peak values measured value: Resetting of the measured min.

and max. distances to the actual measured value.

Select the requested reset function [->] and confirm with [OK].
The following table shows the default values of VEGAPULS 68: