10 Supplement

VEGABAR 55 • Foundation Fieldbus

36736-EN-130321

Electromechanical data - version IP 68
Connection cable between IP 68 instrument and external housing:

Ʋ Configuration

four wires, one suspension wire, one breather capillary,

screen braiding, metal foil, mantle

Ʋ Wire cross-section

0.5 mm² (AWG 20)

Ʋ Wire resistance

< 0.036 Ω/m (0.011 Ω/ft)

Ʋ Standard length

5 m (16.40 ft)

Ʋ Max. length

180 m (590.5 ft)

Ʋ Min. bending radius at 25 °C/77 °F

25 mm (0.985 in)

Ʋ Diameter approx.

8 mm (0.315 in)

Ʋ Colour

Blue

Cable entry/plug

14)

Ʋ External housing

– 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm), 1 x

blind plug M20 x 1.5

or:

– 1␣x plug (depending on the version), 1␣x blind stopper

M20␣x␣1.5

Spring-loaded terminals for wire cross-

section up to

2.5 mm² (AWG 14)

Display and adjustment module
Voltage supply and data transmission

through the sensor

Indication

LC display in dot matrix

Adjustment elements

4 keys

Protection rating

Ʋ unassembled

IP 20

Ʋ mounted into the sensor without cover IP 40

Material

Ʋ Housing

ABS

Ʋ Inspection window

Polyester foil

Voltage supply
Operating voltage

Ʋ Non-Ex instrument

9 … 32 V DC

Ʋ Ex ia instrument

9 … 24 V DC

Ʋ Ex d instrument

9 … 32 V DC

Operating voltage with illuminated display and adjustment module

Ʋ Non-Ex instrument

12 … 32 V DC

Ʋ Ex-ia instrument

12 … 24 V DC

Ex d instrument

12 … 32 V DC

Power supply by/max. number of sensors

Ʋ H1 power supply

max. 32 (max. 10 with Ex)

14)

Depending on the version M12 x 1, according to ISO 4400, Harting, 7/8" FF.