VEGA VEGABAR 55 Foundation Fieldbus User Manual
Page 47
47
10 Supplement
VEGABAR 55 • Foundation Fieldbus
36736-EN-130321
Adjustment range of the zero/span adjustment relating to the nominal measuring range:
Ʋ zero
-20 … +95 %
Ʋ Span
-120 … +120 %
9)
Ʋ Difference between zero and span
max. 120 % of the nominal range
Recommended max. turn down
10 : 1 (no limitation)
Nominal measuring ranges and overload capability in bar/kPa
The specifications are only an overview and refer to the measuring cell. Limitations due to the ma-
terial and version of the process fitting are possible. The specifications on the nameplate apply.
Nominal range
Overload capacity, max.
pressure
Overload capacity, min. pres-
sure
Gauge pressure
0 … +0.1 bar/0 … +10 kPa
+15 bar/+1500 kPa
-1 bar/-100 kPa
0 … +0.2 bar/0 … +20 kPa
+20 bar/+2000 kPa
-1 bar/-100 kPa
0 … +0.4 bar/0 … +40 kPa
+30 bar/+3000 kPa
-1 bar/-100 kPa
0 … +1 bar/0 … +100 kPa
+35 bar/+3500 kPa
-1 bar/-100 kPa
0 … +2.5 bar/0 … +250 kPa
+50 bar/+5000 kPa
-1 bar/-100 kPa
0 … +5 bar/0 … +500 kPa
+50 bar/+5000 kPa
-1 bar/-100 kPa
0 … +10 bar/0 … +1000 kPa
+50 bar/+5000 kPa
-1 bar/-100 kPa
0 … +25 bar/0 … +2500 kPa
+50 bar/+5000 kPa
-1 bar/-100 kPa
-1 … 0 bar/-100 … 0 kPa
+35 bar/+3500 kPa
-1 bar/-100 kPa
-1 … +1.5 bar/-100 … +150 kPa
+50 bar/+5000 kPa
-1 bar/-100 kPa
-1 … +5 bar/-100 … +500 kPa
+50 bar/+5000 kPa
-1 bar/-100 kPa
-1 … +10 bar/-100 … +1000 kPa
+50 bar/+5000 kPa
-1 bar/-100 kPa
-1 … +25 bar/-100 … +2500 kPa
+50 bar/+5000 kPa
-1 bar/-100 kPa
-0.05 … +0.05 bar/-5 … +5 kPa
+15 bar/+1500 kPa
-1 bar/-100 kPa
-0.1 … +0.1 bar/-10 … +10 kPa
+20 bar/+2000 kPa
-1 bar/-100 kPa
-0.2 … +0.2 bar/-20 … +20 kPa
+30 bar/+3000 kPa
-1 bar/-100 kPa
-0.5 … +0.5 bar/-50 … +50 kPa
+35 bar/+3500 kPa
-1 bar/-100 kPa
Absolute pressure
0 … 1 bar/0 … 100 kPa
35 bar/3500 kPa
0 bar abs.
0 … 2.5 bar/0 … 250 kPa
50 bar/5000 kPa
0 bar abs.
0 … 5 bar/0 … 500 kPa
50 bar/5000 kPa
0 bar abs.
0 … 10 bar/0 … 1000 kPa
50 bar/5000 kPa
0 bar abs.
0 … 25 bar/0 … 2500 kPa
50 bar/5000 kPa
0 bar abs.
Nominal measuring ranges and overload capability in psig
The specifications are only an overview and refer to the measuring cell. Limitations due to the ma-
terial and version of the process fitting are possible. The specifications on the nameplate apply.
9)
Values less than -1 bar cannot be set.