VEGA VEGAFLEX 67 (-20…+250°C) Foundation Fieldbus User Manual
Page 53
l
secondary_value_2
-
This is the distance value (sensor_value) with the status of the transducer block
-
It is the input for the AIFB when CHANNEL = 3 is selected
-
The unit is defined in "secondary_value_2"
l
secondary_value_2_unit
-
Selected unit code for "secondary_value_2"
l
sensor_value
-
This is the distance value of the sensor
-
The unit is defined in "sensor_range.Units Index"
l
sensor_range
-
"
sensor_range.Units Index" is the unit for "sensor_value", "max/min_peak_sensor_value",
"C
alibration Highest/Lowest Point" and "empty_vessel_ocrr_dist"
l
simulate_primary_value
l
simulate_secondary_value_1
l
simulate_secondary_value_2
l
Linearization Type
-
Linearization Type, the selectable types are: Linear, User def; Cylindric lying container, Spherical
container
l
tab_op_code
l
tab_index
l
tab_max_number
l
tag_min_number
l
tab_actual_number
l
tab_status
l
tab_x_y_value
l
display_source_selector
-
Selects the type of value, which is displayed on the indicating and adjustment module
l
max_peak_sensor_value
-
Holds the maximum "sensor_value". The unit is defined in "sensor_range.Units Index"
l
min_peak_sensor_value
-
Holds the minimum "sensor_value". The unit is defined in "sensor_range.Units Index"
l
Calibration Highest Point
-
Min./Max. adjustment: this is the upper calibrated point of the sensor_value. It refers to
"
cal_level_hi"
-
The unit is defined in "sensor_range.Units Index"
l
Calibration Lowest Point
-
Min./Max. adjustment: this is the lower calibrated point of the sensor_value. It refers to
"
cal_level_lo"
-
The unit is defined in "sensor_range.Units Index"
l
cal_level_hi
-
Min./Max. adjustment: this is the value of level at "Calibration Highest Point". The unit is
defined in "level_unit
-
When writing "cal_level_hi" and "cal_type" = 1, the "Calibration Highest Point" is automatically set
to "sensor_value"
l
cal_level_lo
VEGAFLEX
67 • Foundation Fieldbus
53