4 Mounting
VEGACAP 69 • - contactless electronic switch
31174-EN-130916
4 Mounting
4.1 General instructions
Make sure that all parts of the instrument coming in direct contact
with the process, especially the sensor element, process seal and
process fitting, are suitable for the existing process conditions, such
as process pressure, process temperature as well as the chemical
properties of the medium.
You can find the specifications in chapter "Technical data" and on the
nameplate.
In general the level switch can be mounted in any position. The instru-
ment must be mounted in such a way that the probe is at the height of
the requested switching point.
Before beginning the welding work, remove the electronics module
from the sensor. By doing this, you avoid damage to the electronics
through inductive coupling.
Use the recommended cables (see chapter "Connecting to power
supply") and tighten the cable gland.
You can give your instrument additional protection against moisture
penetration by leading the connection cable downward in front of the
cable entry. Rain and condensation water can thus drain off. This ap-
plies mainly to outdoor mounting as well as installation in areas where
high humidity is expected (e.g. through cleaning processes) or on
cooled or heated vessels.
Fig. 4: Measures against moisture penetration
Do not hold VEGACAP 69 on the probe. Especially with heavy flange
versions or long rod versions, the sensor can be damaged simply by
the weight of the instrument.
The process fitting must be sealed if there is gauge or low pressure in
the vessel. Before use, check if the seal material is resistant against
the measured product and the process temperature.
The max. permissible pressure is specified in chapter "Technical
data" or on the type label of the sensor.
Suitability for the process
conditions
Switching point
Welding work
Moisture
Transport
Pressure/Vacuum