8 Maintenance and fault rectification

VEGACAL 69 • 4 … 20 mA/HART - two-wire

31178-EN-130917

Error

Cause

Rectification

Current sig-

nal greater than

22 mA or less

than 3.6 mA

Shortcircuit in the

probe, e.g. be-

cause of moisture

in the housing

Remove the electronics module.

Check the resistance between the

marked plug connections. See the fol-

lowing instructions.

Electronics mod-

ule defective

Exchange the instrument or send it in

for repair

Remove the electronics module. Check the resistance between the

two plug connections.
There must no longer be a connection (high impedance). If there is

still a connection - exchange the instrument or return it for repair

1 2

3

Fig. 24: Check the resistance in the probe
1 Shielding

2 Probe

3 Ground potential

In Ex applications, the regulations for the wiring of intrinsically safe

circuits must be observed.

Error

Cause

Rectification

E013

no measured val-

ue available

– Probe insulation damaged, short-

circuit due to permeating, conduc-

tive medium

– Exchange the instrument or send it

in for repair

Shortcircuit in the

probe, e.g. be-

cause of moisture

in the housing

– Remove the electronics module out

of the probe and check the resistor

between the two marked plug con-

nections according to the figure in

paragraph "Check the resistance in

the probe".

– There should be no contact

between any of the connections

(high resistance)

– If there is still a connection -

exchange the instrument or return

it for repair

Check the resistance in

the probe

Error messages via the

display and adjustment

module