epending on the tube diameter or tube length, one or several spacers

can be mounted. With cable probes, the cable can also be strained to
avoid contact with the tube.

K

eep in mind that buildup can form on the spacers. Strong buildup can

influence the measurement.

M

icrowaves can penetrate plastics. For process technical reasons,

plastic standpipes are problematic. If durability is no problem, then we
recommend the use of metal standpipes.

1

Fig. 5: Position of the spacer

1

Spacer

Note:
M

easurement in a standpipe is not recommended for very adhesive

products.

M

ake sure that the probe is not subjected to strong lateral forces.

M

ount VEGAFLEX 63 at a position in the vessel where no

disturbances, e.g. from filling openings, agitators, etc., can occur.

Inflowing medium