When used on a control system, the following values apply:

l

Mode min.

-

Vibrating element uncovered - 16 mA ±1 mA

-

Vibrating element covered - 8 mA ±1 mA

l

Mode max.

-

Vibrating element uncovered - 8 mA ±1 mA

-

Vibrating element covered - 16 mA ±1 mA

Control lamp for indication of the switching status

l

green = 8 mA

l

red = 16 mA

l

red (flashing) = Failure (< 2.3 mA)

6

.3 Function chart

Level switch VEGAWAVE 62
The following chart provides an overview of the switching conditions
depending on the adjusted mode and level.

Mode on the
sensor

Level

Signal current -
Sensor

Signal lamp -
sensor

Max.
Overflow protec-
tion

8 mA

Green

Max.
Overflow protec-
tion

approx. 16 mA

Red

Min.
Dry run protection

approx. 8 mA

Green

Min.
Dry run protection

approx. 16 mA

Red

Fault message
(min./max. mode)

any

<

2.3 mA

flashes red

Signal lamp (5)

VEGAWAVE

62 • - two-wire

21

6 Set up

32255

-

EN

-120418