Input variable

Measured variable

Level of liquids

Min. dielectric figure of the medium

ε

r

>

1.4

2

4

5

3

1

2

4

5

3

1

Fig. 16: Measuring ranges of VEGAFLEX 65

1

Reference plane

2

Probe length L

3

Measuring range (default setting refers to the measuring range in water)

4

Upper dead band (see diagrams under Accuracy - grey section)

5

Lower dead band (see diagrams under Accuracy - grey section)

Output variable

Output signal

digital output signal, format according to IEEE-754

Cycle time

min. 1 s (dependent on the parameter setting)

Sensor address

126 (default setting)

Current value

10 mA, ±0.5 mA

Damping (63 % of the input variable)

0 … 999 s, adjustable

Fulfilled NAMUR recommendations

NE

43

Resolution, digital

>

1 mm (0.039 in)

Accuracy (according to DIN EN 60770-1)

Process reference conditions according to DIN EN 61298-1

-

Temperature

+

18 … +30 °C (+64 … +86 °F)

VEGAFLEX

65 • Profibus PA

41