VEGA VEGAFLEX 62 Profibus PA User Manual
Page 33
Basic adjustment
If the function "Reset" is carried out, the sensor resets the values of the
following menu items to the reset values (see chart):
2)
The following values will be reset:
Function
Reset value
Max. adjustment
Distance, upper dead zone
Min. adjustment
Distance, supplied sensor length
Min. adjustment - Cable version
Distance, lower dead zone
Damping ti
0 s
Linearisation
linear
Sensor-TAG
Sensor
Display
PA-Out 1
Channel (PV)
lin %
Additional PA value (PV)
lin %
Out-Scale-Unit
%
PV-Out-Scale
0.00 lin % = 0.0 %
100.0 lin % = 100 %
The values of the following menu items are not reset to the reset
values (see chart) with "Reset":
Function
Reset value
Sensor address
No reset
Language
No reset
Factory setting
Like basic adjustment, in addition, special parameters are reset to
default values.
3)
Pointer
The min. and max. distance values are reset to the actual value.
Additional adjustment and diagnosis options such as e.g. scaling,
simulation or trend curve presentation are shown in the following menu
schematic. You will find a detailed description of these menu items in
the operating instructions manual "Indicating and adjustment module".
2)
Sensor-specific basic adjustment.
3)
Special parameters are parameters which are set customer-specifically on
the service level with the adjustment software PACTware.
Reset
Optional settings
VEGAFLEX
62 • Profibus PA
33
6 Set up with the indicating and adjustment module PLICSCOM
31839
-
EN
-100426