8 Maintenance and fault rectification

VEGACAL 67 • 4 … 20 mA/HART - two-wire

31758-EN-130917

Error

Cause

Rectification

E036

no operable sen-

sor software

Carry out a software update or send

instrument for repair

Depending on the reason for the fault and the measures taken, the

steps described in chapter "Set up" may have to be carried out again.

8.3 Exchanging the electronics module

If the electronics module is defective, it can be replaced by the user.
In Ex applications only one instrument and one electronics module

with respective Ex approval may be used.
If there is no electronics module available on site, one can be ordered

from the VEGA agency serving you.

The new electronics module must be loaded with the order data of the

sensor. These are the options:

At the factory by VEGA

Or on site by the user

In both cases, the sensor serial number is needed. The serial num-

bers are stated on the type label of the instrument or on the delivery

note.
Information:

When loading on site, first of all the order data must be downloaded

from the Internet (see operating instructions manual "Electronics

module").

The electronics modules are adapted to the respective sensor and

differ in their signal output or in their power supply. You can find a suit-

able electronics module in the following overview.
The oscillators differ only in their signal output and are suitable for all

series 60 sensors.
The following types are available:

CL-E60H (4 … 20 mA/HART)

CL-E60P (Profibus PA)

CL-E60F (Foundation Fieldbus)

8.4 Shortening the electrode

The probe (cable) can be shortened by any length.

1. Loosen the two pins on the gravity weight (hexagon) and remove

the pins.

2. Pull the cable out of the gravity weight.
3. To avoid splicing of the steel cable, tin the cable before shortening

with a soldering iron and tighten the wire.

4. Shorten the cable with a cut-off wheel or metal saw at the lower

end. Make sure the length is correct before shortening.

Reaction after fault recti-

fication

Sensor serial number

Assignment

Shortening the electrode