beautypg.com

VEGA VEGAFLEX 61 4 … 20 mA_HART two-wire User Manual

Page 32

background image

these vessels. They represent the correlation between the level
percentage and vessel volume. By activating the appropriate curve,
the volume percentage of the vessel is displayed correctly. If the
volume should not be displayed in percent but e.g. in l or kg, a scaling
can be also set in the menu item "Display".

L

inearisation curve

linear

E

nter the requested parameters via the appropriate keys, save your

settings and jump to the next menu item with the [->] key.

Caution:
N

ote the following, if VEGAFLEX 61 is used as part of an overfill

protection system according to WHG:

I

f a linearisation curve is selected, the measuring signal is no longer

compulsorily linear proportional to the level. This must be taken into
consideration by the user, particularly when adjusting the switching
point on the level switch.

I

n this menu item you can enter an unambiguous designation for the

sensor, e.g. the measurement loop name or the tank or product
designation. In digital systems and in the documentation of larger
plants, a singular designation should be entered for exact identification
of individual measuring points.

S

ensor-TAG

Sensor

W

ith this menu item, the Basic adjustment is finished and you can now

jump to the main menu with the [ESC] key.

H

igh sockets or vessel installations, such as e. g. struts or agitators as

well as buildup and weld joints on the vessel walls, cause interfering
reflections that can impair the measurement. A false echo storage
detects and marks these false echoes, so that they are no longer taken
into account for the level measurement. A false echo memory should
be created with low level so that all potential interfering reflections can
be detected.

G

ating out of false signals

C

hange now?

Sensor-TAG

Gating out of false sig-
nals

32

VEGAFLEX

61 • 4 … 20

mA/HART two-wire

6 S

et up with the indicating and adjustment module PLICSCOM

31833

-EN

-100426