Transmission rate
31.25 Kbit/s
Current value
10 mA, ±0.5 mA
Resolution, digital
> 1
mm (0.039 in)
Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1
-
Temperature
+18
… +30 °C (+64 … +86 °F)
-
Relative humidity
45 … 75 %
-
Air pressure
+860
… +1060 mbar/+86 … +106 kPa
(+12.5 … +15.4 psig)
Installation reference conditions
-
Min. distance to installations
> 500
mm (19.69 in)
-
Vessel
metallic, ø 1 m (3.281 ft), centric installation,
process fitting flush with the vessel ceiling
-
Medium
Water/Oil (dielectric figure ~2.0)
-
Installation
Probe end does not touch the vessel bottom
Sensor parameter adjustment
Gating out of false signals carried out
Deviation
see diagrams
Depending on the installation conditions, there can
be deviations which can be rectified with an
adaptation of the adjustment or a change of the
measured value offset in the DTM service mode.
L
0
-2 mm (-0.079
")
2 mm (0.079
")
-10 mm (0.394
")
5 mm (0.197
")
0,15 m (5.906
"
)
0,03 m (1.181
"
)
0,05 m
(1.969
")
1
Fig. 17: Deviation VEGAFLEX 65 in coax version in water
1
Dead zone - no measurement possible in this area
L
Probe length