Ʋ Max.

750 VA AC, 54 W DC
If inductive loads or stronger currents are switched

through, the gold plating on the relay contact surface will

be permanently damaged. The contact is then no longer

suitable for switching low-level signal circuits.

Potential separation

> 500 V DC

Contact material (relay contacts)

AgNi (Au plated) or AgSnO (Au plated)

Modes (switchable)

A (overfill protection)/B (dry run protection)

Switching delay

Ʋ When immersed

0.7 s

Ʋ When laid bare

0.7 s

Ʋ In case of failure

1 s

Ambient conditions
Ambient temperature on the housing

-40 … +80 °C (-40 … +176 °F)

Storage and transport temperature

-40 … +80 °C (-40 … +176 °F)

Process conditions
Process pressure

Unpressurized

Process temperature VEGACAP 98 of PP -30 … +80 °C (-22 … +176 °F)
Dielectric constant

≥ 1.5

Electromechanical data
Cable entry/plug (dependent on the version)

Ʋ Single chamber housing

– 1 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm),

1 x blind plug M20 x 1.5; attached 1 x cable entry

M20 x 1.5

or:

– 1 x cable entry ½ NPT, 1 x blind plug ½ NPT, 1 x cable

entry ½ NPT

or:

– 1 x plug M12 x 1; 1 x blind plug M20 x 1.5

Screw terminals

for wire cross-section up to 1.5 mm² (AWG 16)

Adjustment elements
Mode switch

Ʋ A

Min. detection or dry run protection

Ʋ B

Max. detection or overflow protection

Potentiometer

Switching point adaptation

Voltage supply
Operating voltage

20 … 253 V AC, 50/60 Hz, 20 … 72 V DC (at

U >60 V DC, the ambient temperature can be max.

50 °C/122 °F)

Power consumption

1 … 9 VA (AC), approximately 1.5 W (DC)