Fig. 24: Deviation VEGAFLEX 67 in coax version

1

Dead zone - no measurement possible in this area

L

Probe length

Influence of the ambient temperature to the sensor electronics

Temperature drift

0.03 %/10 K relating to the max. measuring range
or max. 0.3 %

Temperature drift - Digital output

3 mm/10 K relating to the max. measuring range or
max. 10 mm

Ambient conditions

Ambient, storage and transport temperature

-40 … +80 °C (-40 … +176 °F)

Process conditions

Process pressure

-1 … +100 bar/-100 … +10000 kPa (-
-14.5 … +1450 psig), depending on the process
fitting

Process temperature (thread or flange tem-
perature)

-20 … +250 °C (-4 … +482 °F)

The measurement error from the process condi-
tions is in the specified pressure and temperature
range of below 1 %.