more than 1 m (3.281 in) length, you must secure the probe by
fastening a suitable isolated brace or guy directly above the end of the
rod.

I

f there is a danger of the probe touching the vessel wall during

operation due to product movements or agitators etc., the measuring
probe should be securely fixed.

I

n the gravity weight there is a thread (M12), e.g. for a ring bolt

(

optional) - (article no. 2.27424).

M

ake sure that the probe cable is not completely taut. Avoid tensile

loads on the cable.

A

void undefined cable-vessel connections, i.e. the connection must be

either grounded reliably or isolated reliably. Any deviation from this
requirement can lead to measurement errors.